Richardson Fire Department
Fire Marshal’s Office 136 N Greenville Ave., Richardson, TX 75081
In-Duct Smoke Detector Testing Requirements
|
The Richardson Fire Department requires in-duct smoke detectors that are supervised by a fire alarm system to be tested in accordance with the National Fire Alarm Code [see below] and the manufacturer's instructions.
|
|
|
NFPA 72, 2007 edition, Table 10.4.2.2 Test Methods
|
|
|
(4) Duct type
|
Air duct detectors shall be tested or inspected to ensure that the device will sample the airstream. The test shall be made in accordance with the manufacturer’s published instructions
|
|
|
|
|
|
|
The following must be submitted to the Fire Department, with the Fire Protection System Permit number indicated, as part of the final acceptance of the system:
- A copy of the manufacturer’s instructions, describing the test methods and the acceptable range;
- The individual measurements and differential calculations for each unit. The measurements and results must be on letterhead, signed by a representative of the fire alarm or HVAC contractor.
If you have any questions, please contact the Richardson Fire Department, Fire Marshal’s Office at (972)744-5750.